Riello Sentinel Pro (SEP 1500) - On Line UPS
Online UPS
Sentinel Pro has a unique and modern design with improved performance, developed by Riello UPS and the research and development department. Sentinel Pro uses on-line double conversion technology, resulting in: the highest levels of reliability and maximum protection for critical loads such as servers, IT and telecommunications equipment.
The display face has been completely redesigned, and an LCD screen has been added that shows input and output voltages, battery readings and UPS operating states. The inverter and microprocessor control circuit have been completely redesigned and provide greater efficiency and more setting options. Maximum expandability: the Sentinel Pro series provides as standard a USB port and an expansion port for the protocol converter or card with relay contacts.
With energy savings in mind, the Sentinel Pro is also equipped with a stop button to reduce energy consumption to zero during extended periods of inactivity (ECO LINE). The Sentinel Pro is available in 700 VA, 1000 VA, 1500 VA, 2200 VA and 3000 VA models.
SEP 700 MODELS
POWER 700VA/560 W
ENTRANCE
Nominal Voltage 220-230-240 VAC
Voltage range without battery operation 140 – 276 VAC @50% LOAD / 184 – 276 VAC @ 100% LOAD
Maximum allowable voltage 300 VAC
Nominal Frequency 50/60 Hz
Frequency range 50 Hz ± 5% / 60 Hz ± 5%
Power factor > 0.99
Current distortion ≤7%
BY PASS
Voltage Tolerance 180 – 264 VAC
Frequency Tolerance Selectable Frequency (±1.5Hz to ±5Hz adjustable)
Overload 125% for 5 seconds, 150% for 1 second
EXIT
Voltage distortion with linear load / with non-linear load < 2% / < 4%
Frequency Selectable: 50 Hz or 60 Hz or automatic
Static Variation ± 1%
Dynamic Variation ≤ 5% in 20 msec.
Sine Waveform
3:1 peak current factor
ECO Performance and Smart Active Functions 98%
ACCUMULATORS
Type VRLA AGM lead sealed maintenance free
Recharge time 2-4 hours
OTHER CHARACTERISTICS
Net weight (kg) 10.9
Dimensions WxDxH (mm) 158 x 422 x 235
300 joules surge protection
Protections From overvoltages – Short circuit – overvoltage – low voltage – Temperature – battery overdischarge
USB / RS232 DB9 communications with contacts / socket for communication card
Number of outputs 4 x IEC 320 C13
Design regulations Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 620040-2 category C2 and Directives 2004/108/EL
Operating Temperature 0 – 40 ° C
Humidity <95% non-condensing
Black color
Noise level at a distance of 1 m (ECO Mode) < 40 dBA
Standard equipment Power cord, IEC-IEC cable, USB cable, safety manual, quick start guide